Generated ontology API reference#
The class signatures, inherited members, and ontology definitions below come
from generated Python packages at build time. Use a class’s .meta property
to inspect its source IRI, definition, parents, and effective property specs.
The Class catalog lists every importable S223 and WaTr class.
S223 equipment and connection points#
- class plumb.s223.Damper(name=None, *, actuated_by_property=(), cnx=(), connected=(), connected_from=(), connected_through=(), connected_to=(), contains_=(), executes=(), has_connection_point=(), has_optional_connection_point=(), has_physical_location=(), has_property=(), has_role=(), medium=(), label=None, comment=None, model=None)#
A piece of Equipment inserted into an air distribution system permitting modification of the air resistance of the system and consequently changing the airflow rate or shutting off the airflow.
Ontology: S223 — http://data.ashrae.org/standard223#Damper
- class plumb.s223.Fan(name=None, *, actuated_by_property=(), cnx=(), connected=(), connected_from=(), connected_through=(), connected_to=(), contains_=(), executes=(), has_connection_point=(), has_optional_connection_point=(), has_physical_location=(), has_property=(), has_role=(), medium=(), label=None, comment=None, model=None)#
A piece of Equipment that causes a gas (e.g., air) to flow.
Ontology: S223 — http://data.ashrae.org/standard223#Fan
- class plumb.s223.Chiller(name=None, *, actuated_by_property=(), cnx=(), connected=(), connected_from=(), connected_through=(), connected_to=(), contains_=(), executes=(), has_connection_point=(), has_optional_connection_point=(), has_physical_location=(), has_property=(), has_role=(), medium=(), label=None, comment=None, model=None)#
A piece of Equipment that removes heat from a liquid coolant via a vapor-compression, adsorption refrigeration, or absorption refrigeration cycles.
Ontology: S223 — http://data.ashrae.org/standard223#Chiller
WaTr equipment#
- class plumb.watr.Pump(name=None, *, actuated_by_property=(), cnx=(), connected=(), connected_from=(), connected_through=(), connected_to=(), contains_=(), executes=(), has_connection_point=(), has_optional_connection_point=(), has_physical_location=(), has_process=(), has_property=(), has_role=(), has_treatment_objective=(), medium=(), label=None, comment=None, model=None)#
A device used to move fluids by mechanical action. Unlike s223:Pump, which asks for water, oil or refrigerant, it accepts any s223:Mix-Fluid, so it covers sludge and other slurries.
Ontology: WATR — https://watermetadata.org/ontology/watr#Pump
- class plumb.watr.Tank(name=None, *, actuated_by_property=(), cnx=(), connected=(), connected_from=(), connected_through=(), connected_to=(), contains_=(), executes=(), has_connection_point=(), has_optional_connection_point=(), has_physical_location=(), has_process=(), has_property=(), has_role=(), has_treatment_objective=(), medium=(), label=None, comment=None, model=None)#
A vessel with at least one fluid connection point. A storage tank may use a single bidirectional port; flow-through subclasses require the appropriate inlet and outlet points.
Ontology: WATR — https://watermetadata.org/ontology/watr#Tank
- class plumb.watr.CoagulationBasin(name=None, *, actuated_by_property=(), cnx=(), connected=(), connected_from=(), connected_through=(), connected_to=(), contains_=(), executes=(), has_connection_point=(), has_optional_connection_point=(), has_physical_location=(), has_process=(), has_property=(), has_role=(), has_treatment_objective=(), medium=(), label=None, comment=None, model=None)#
A basin where coagulation occurs to destabilize particles in water
Ontology: WATR — https://watermetadata.org/ontology/watr#CoagulationBasin
- class plumb.watr.FlocculationBasin(name=None, *, actuated_by_property=(), cnx=(), connected=(), connected_from=(), connected_through=(), connected_to=(), contains_=(), executes=(), has_connection_point=(), has_optional_connection_point=(), has_physical_location=(), has_process=(), has_property=(), has_role=(), has_treatment_objective=(), medium=(), label=None, comment=None, model=None)#
A tank where flocculation occurs to aggregate particles in water
Ontology: WATR — https://watermetadata.org/ontology/watr#FlocculationBasin
- class plumb.watr.RapidSandFilter(name=None, *, actuated_by_property=(), cnx=(), connected=(), connected_from=(), connected_through=(), connected_to=(), contains_=(), executes=(), has_connection_point=(), has_optional_connection_point=(), has_physical_location=(), has_process=(), has_property=(), has_role=(), has_treatment_objective=(), medium=(), label=None, comment=None, model=None)#
A type of media filter that uses sand as the filter medium and operates at high filtration rates.
Ontology: WATR — https://watermetadata.org/ontology/watr#RapidSandFilter
- class plumb.watr.ChlorinationUnit(name=None, *, actuated_by_property=(), cnx=(), connected=(), connected_from=(), connected_through=(), connected_to=(), contains_=(), executes=(), has_connection_point=(), has_optional_connection_point=(), has_physical_location=(), has_process=(), has_property=(), has_role=(), has_treatment_objective=(), medium=(), label=None, comment=None, model=None)#
A unit that uses chlorine or chlorine compounds for disinfection.
Ontology: WATR — https://watermetadata.org/ontology/watr#ChlorinationUnit
WaTr process and objective vocabulary#
- class plumb.watr.Process(name=None, *, label=None, comment=None, model=None, **props)#
A physical, chemical, or biological activity performed by a piece of equipment or by a system.
Ontology: WATR — https://watermetadata.org/ontology/watr#Process
- class plumb.watr.Process_Settling(name=None, *, label=None, comment=None, model=None, **props)#
A unit process that allows solids to settle out of water by gravity.
Ontology: WATR — https://watermetadata.org/ontology/watr#Process-Settling
- class plumb.watr.TreatmentObjective(name=None, *, label=None, comment=None, model=None, **props)#
An objective that a piece of equipment or a system is intended to achieve.
Ontology: WATR — https://watermetadata.org/ontology/watr#TreatmentObjective
- class plumb.watr.TreatmentObjective_Clarification(name=None, *, label=None, comment=None, model=None, **props)#
Production of a clarified liquid stream by removing suspended solids from it. The objective of every clarifier, whatever the stage it serves and whatever mechanism it separates by.
Ontology: WATR — https://watermetadata.org/ontology/watr#TreatmentObjective-Clarification
- class plumb.watr.SedimentationTank(name=None, *, actuated_by_property=(), cnx=(), connected=(), connected_from=(), connected_through=(), connected_to=(), contains_=(), executes=(), has_connection_point=(), has_optional_connection_point=(), has_physical_location=(), has_process=(), has_property=(), has_role=(), has_treatment_objective=(), medium=(), label=None, comment=None, model=None)#
A tank in which suspended solids separate from water by settling under gravity
Ontology: WATR — https://watermetadata.org/ontology/watr#SedimentationTank
Generated domain configurations#
- class plumb.watr.drinking_water.CoagulationStage(name=None, *, actuated_by_property=None, cnx=None, connected=None, connected_from=None, connected_through=None, connected_to=None, contains_=None, executes=None, has_connection_point=None, has_optional_connection_point=None, has_physical_location=None, has_process=None, has_property=None, has_role=None, has_treatment_objective=None, medium=None, label=None, comment=None, model=None)#
Coagulant addition and particle destabilization ahead of flocculation.
- class plumb.watr.drinking_water.FlocculationStage(name=None, *, actuated_by_property=None, cnx=None, connected=None, connected_from=None, connected_through=None, connected_to=None, contains_=None, executes=None, has_connection_point=None, has_optional_connection_point=None, has_physical_location=None, has_process=None, has_property=None, has_role=None, has_treatment_objective=None, medium=None, label=None, comment=None, model=None)#
Gentle mixing to form flocs that can settle in the clarifier.
- class plumb.watr.drinking_water.ClarificationStage(name=None, *, actuated_by_property=None, cnx=None, connected=None, connected_from=None, connected_through=None, connected_to=None, contains_=None, executes=None, has_connection_point=None, has_optional_connection_point=None, has_physical_location=None, has_process=None, has_property=None, has_role=None, has_treatment_objective=None, medium=None, label=None, comment=None, model=None)#
Settles flocs and separates clarified water from a sludge withdrawal.
- class plumb.watr.drinking_water.RapidSandFiltrationStage(name=None, *, actuated_by_property=None, cnx=None, connected=None, connected_from=None, connected_through=None, connected_to=None, contains_=None, executes=None, has_connection_point=None, has_optional_connection_point=None, has_physical_location=None, has_process=None, has_property=None, has_role=None, has_treatment_objective=None, medium=None, label=None, comment=None, model=None)#
Filters clarified water through sand; spent backwash leaves separately during cleaning.
- class plumb.watr.drinking_water.ChlorinationStage(name=None, *, actuated_by_property=None, cnx=None, connected=None, connected_from=None, connected_through=None, connected_to=None, contains_=None, executes=None, has_connection_point=None, has_optional_connection_point=None, has_physical_location=None, has_process=None, has_property=None, has_role=None, has_treatment_objective=None, medium=None, label=None, comment=None, model=None)#
Chlorine dosing and a contact stage with the objective of disinfection.
- class plumb.s223.hvac.AirWaterCoolingCoil(name=None, *, actuated_by_property=None, cnx=None, connected=None, connected_from=None, connected_through=None, connected_to=None, contains_=None, executes=None, has_connection_point=None, has_optional_connection_point=None, has_physical_location=None, has_property=None, has_role=None, medium=None, label=None, comment=None, model=None)#
A cooling coil with separate air and water inlets and outlets.
- class plumb.watr.asm2d.AerobicStage(name=None, *, actuated_by_property=None, cnx=None, connected=None, connected_from=None, connected_through=None, connected_to=None, contains_=None, executes=None, has_connection_point=None, has_optional_connection_point=None, has_physical_location=None, has_process=None, has_property=None, has_role=None, has_treatment_objective=None, medium=None, label=None, comment=None, model=None)#
- class plumb.watr.asm2d.AerobicDesign(*, volume=1333.0, oxygen_transfer_coefficient)#
Aerobic basin volume in m³ (default 1333) and oxygen transfer coefficient KLa in h⁻¹.
- volume = 1333.0#
Volume; ; default unit http://qudt.org/vocab/unit/M3; source https://watermetadata.org/plumb/asm2d#AerobicVolumeShape
- oxygen_transfer_coefficient#
Oxygen transfer coefficient; ; default unit http://qudt.org/vocab/unit/PER-HR; source https://watermetadata.org/plumb/asm2d#OxygenTransferCoefficientShape
- class plumb.watr.seawater_ro.MembraneDesign(*, membrane_area, spacer_porosity, channel_height, stage_width, salt_permeability)#
MembraneDesign quantities with nominal aspects and shape-declared default units.
- membrane_area#
Membrane area; ; default unit http://qudt.org/vocab/unit/M2; source https://watermetadata.org/plumb/seawater-ro#MembraneDesign_membrane_areaShape
- spacer_porosity#
Feed spacer porosity; ; default unit http://qudt.org/vocab/unit/UNITLESS; source https://watermetadata.org/plumb/seawater-ro#MembraneDesign_spacer_porosityShape
- channel_height#
Membrane channel height; ; default unit http://qudt.org/vocab/unit/M; source https://watermetadata.org/plumb/seawater-ro#MembraneDesign_channel_heightShape
- stage_width#
Membrane width per stage; ; default unit http://qudt.org/vocab/unit/M; source https://watermetadata.org/plumb/seawater-ro#MembraneDesign_stage_widthShape
- salt_permeability#
Salt permeability coefficient; ; default unit http://qudt.org/vocab/unit/M-PER-SEC; source https://watermetadata.org/plumb/seawater-ro#MembraneDesign_salt_permeabilityShape
Common entity API#
- class plumb.Entity(name=None, *, label=None, comment=None, model=None, **props)#
Base class for all generated ontology classes.
Construction requires an active
Model(either ambient, viawith Model(...), or passed asmodel=). The first argument is the entity’s local name; the model’s namespace turns it into an IRI at serialization time. When omitted, a name is auto-generated per model as<class>_<n>(vav_1,vav_2, …).Reserved attribute names (
name,type,label,comment,meta,model,ports,describe_ports, the find and walk methods, …; seeplumb.gen.naming.RESERVED): ontology properties that would collide are renamed by the generator’s collision policy.- property name#
Local name; combined with the model namespace to mint the IRI.
- property type#
Python class name, such as
"Duct".Use
meta.irifor the ontology class IRI.
- property label#
Human-readable label (
rdfs:label); defaults to the name.
- property comment#
Free-text note serialized as
rdfs:comment.
- contains(*children, via=None)#
Declare that this entity contains the given entities.
The predicate is negotiated per (container, child) class pair from the package’s containment table; pass
via='<property>'to pick one explicitly. Returnsselffor chaining.
- quantity(name, value, *, unit=None, kind, capability='static', label=None, **properties)#
Create and attach a named S223 quantifiable property to this object.
capabilityselects a static, observable, or actuatable property. Measurement aspects are independent; passhas_aspectexplicitly. AQuantityAmountsupplies its own unit. The returned property is an ordinary model entity.
- apply_properties(schema, *, prefix=None)#
Attach fresh properties from a generated RDF/SHACL value schema.
- port(name, *, direction, medium=None, label=None)#
Declare a named deferred connection point for solver negotiation.
- property ports#
Concrete connection points and authored deferred ports on this entity.
The authored model can contain both generated ConnectionPoint entities and PortHandle intentions. A resolved snapshot exposes concrete points here after the solver has materialized the deferred ones.